A cyberattack reached the equipment keeping food cold at French supermarkets overnight on October 11–12. Coopérative U chief executive Dominique Schelcher confirmed that refrigeration installations at several stores in the network were affected. On October 12, France’s national computer emergency response team, CERT-FR, separately warned of numerous compromises of Danfoss AK-SM and AK-SC systems.
Updated October 13: CERT-FR has expanded the equipment scope and revised its recovery guidance. Operators should remove public internet exposure and follow the appropriate recovery path below; restoring cooling alone does not establish secure control.
The incident reached the cold chain
Schelcher said teams were working with refrigeration specialists to restore operations, and that an investigation would need to establish what happened. His statement identifies the affected function precisely: the installations producing refrigeration, essential to preserving fresh food and maintaining supplies. It does not give a final store count or loss estimate.
That distinction matters. The retailer described a disruption to physical equipment, rather than simply an unavailable shopping website. Restoring a web service and restoring trustworthy control of a refrigeration installation are different jobs. The latter has to involve the people responsible for operating and configuring the equipment.
CERT-FR’s updated alert names Danfoss AK-SM and AK-SC, Copeland xweb and Dixell xweb but does not identify a particular exploit, firmware version or CVE as the cause. It warns that exposing a management interface directly to the internet violates good practice. Where remote administration is essential, restricting access to trusted IP addresses is an initial temporary measure.
The useful question for an operator is therefore concrete: who can reach the controller’s management interface, and who has authority to change its configuration? The alert establishes the need to close that access path; it does not establish how every affected store was entered.
What the primary statements establish
| Confirmed point | Limit of the evidence |
|---|---|
| Coopérative U reported overnight disruption to refrigeration at several stores. | Its statement does not quantify damaged stock, total losses or the final number of affected stores. |
| CERT-FR’s October 13 version lists Danfoss AK-SM/AK-SC, Copeland xweb and Dixell xweb. | The alert does not attribute the incident to a named group or a specific vulnerability. |
| CERT-FR removes public exposure and separates compromised and non-compromised equipment. | A factory reset alone is insufficient for exposed unsupported equipment without security fixes. |
November 13 update: separate controller flaws change the access decision
Ireland’s NCSC distinguishes the continuing European refrigeration incidents from separate Midnight Blue research into six previously unknown pre-authentication remote-code-execution flaws in Danfoss AK-SM800A controllers, affecting firmware up to and including 5.3.2. Its November 13 advisory says the research could allow control without valid credentials. It does not identify those flaws as the proven entry method in the French incident. [9]
At the advisory’s publication, no CVE identifiers or patches were available and coordinated disclosure was ongoing. NCSC also describes a Strict session-control flaw and researcher-reported persistence that could survive a factory reset or firmware update, as well as the possibility of making a device inoperable. These are the findings described on November 13, not a claim that every refrigeration model or every affected store has that firmware. [9]
The practical change is that a password change, Strict Mode or a firmware update alone cannot be treated as enough protection for an internet-exposed controller. Remove direct public management access and use a secured VPN or equivalent protected network for necessary maintenance. Restricting access to known service-provider IPs is a temporary containment measure. With the refrigeration specialist, compare temperature setpoints, defrost schedules, alarm settings and remote accounts against a known-good configuration; current cooling does not establish secure control. This supplements the dated CERT-FR recovery branches below rather than replacing them.
November 9 update: France attributes the attack and reports fires
On November 9, France’s cybersecurity agency ANSSI said the October 11–12 operation targeted refrigeration controllers at about 700 retail sites in France. Investigators found that attackers changed the defrost settings to high temperatures. ANSSI reported lost stock and at least 15 fires. The approximately 700 sites are the scope of this attack, separate from the count of internet-exposed devices in the Unit 42 survey below.[8]
France attributed the attack to Shahid Kaveh, a cyber unit affiliated with the electronic and cyber command of Iran’s Islamic Revolutionary Guard Corps. France’s cyber crisis coordination center cited infrastructure characteristics, use of the FOFA scanning tool alongside other evidence, Persian-language traces and amplification by a propaganda outlet linked to the unit. It also linked concurrent targeting of several small French hydroelectric sites to the same operation. These findings concern the French incident; they do not establish that the same actor caused the later Swedish outages.[8]
The physical damage explains why a return to normal cooling is only one recovery check. Operators should also compare defrost temperatures and schedules against their known-good settings before restoring remote management.
November 6 update — Unit 42 measured internet exposure
Unit 42 reported that its Cortex Xpanse scan on November 5–6 found more than 5,000 internet-exposed devices from manufacturers named in the CERT-FR alert. For France, it counted 1,853 exposed devices on October 1–15, 558 on October 16–31 and 316 on November 1–6.
These are exposure measurements. The scan does not establish whether a device ran a vulnerable firmware version or whether anyone broke into it. For an operator, the first step is to check which management interfaces are reachable from outside the network, then confirm their exact models and firmware. Review controller logs separately for unexpected changes to setpoints, defrost cycles or accounts.
November 5 update: US agencies warn about cold-chain controls
CISA, the FBI, HHS, USDA and the Department of Transportation warn that malicious activity is targeting industrial refrigeration and cold-chain monitoring worldwide. Their joint fact sheet describes controllers being forced into heating or defrost cycles and a separate denial-of-view risk: operators may lose trustworthy temperature visibility. It does not establish one actor behind all the European incidents or a combined victim total.
For operators, restoring cooling is only part of recovery. Remove public controller exposure, isolate operational technology from business networks, restrict necessary remote access, replace default credentials and update supported firmware. The agencies also call for safe downstream setpoint limits and alerts for deviations, so a controller change cannot silently push equipment beyond operating bounds. Review logs or network traffic and test offline backups. These are safeguards for industrial systems, not instructions to reset a household refrigerator.
November 3 update: restored stores, disconnected controllers
Coop told Reuters that its seven affected Swedish stores were operating again, while refrigeration systems remained disconnected from the internet. ICA said all 23 affected stores had equipment outside its centrally managed store network. Danfoss advised against direct internet access to its systems. These company statements add a concrete containment distinction: reopening a store does not mean reconnecting its controllers or fixing the underlying exposure. They do not establish a single attacker across every country.
November 2 update: Swedish outages, unconfirmed cause
ICA and Coop told AFP that overnight refrigeration failures forced Swedish stores to discard food. Coop counted six affected stores; ICA had no total. A Sjöbo store blamed hacking and reported a 50°C setting, but neither chain confirmed a cyberattack. Equipment and entry method remained unverified. These accounts do not establish a connection to the French attack or a shared recovery path.
October 13 update: equipment scope and recovery paths
CERT-FR now also names Copeland xweb and Dixell xweb, alongside Danfoss AK-SM and AK-SC. Its revised guidance separates equipment that has not been compromised from compromised installations. In both cases, remove public internet exposure first; check insurance obligations before interrupting data reporting to the refrigeration service provider.
- Equipment not compromised: check the complete configuration, especially defrost schedules. Restore remote access through a secure VPN or protected network, then apply manufacturer hardening and firmware guidance.
- Compromised equipment: factory-reset the unit after removing exposure. Restore access through a secure VPN or protected network, reconfigure it for service and apply manufacturer hardening.
Emergency firewall filtering to a service provider’s source IP addresses is temporary, not a permanent access design. For Danfoss equipment, CERT-FR specifically includes firmware updates, Strict security mode and changing default passwords. It warns that a reset alone leaves unsupported, unpatched equipment vulnerable to reinfection if it remains internet-exposed.
Credential rotation and account review were explicit steps in the October 12 version and remain useful recovery checks with the service provider. They should not be mistaken for the revised alert’s complete procedure. Likewise, normal cooling does not establish that management access and defrost settings are trustworthy.
The separately retained CERT-FR industrial hardening document provides background on authenticated VPN access, default credentials and patching. The October 12 alert linked to it; the current version gives the refrigeration-specific branches above.
The broader pattern of remotely accessible equipment also appears in the LeakySensey investigation into compromised routers. That is a separate case, with a different purpose; here, the established consequence is disruption to refrigeration.
The French incident makes control of physical equipment the central security issue. Operators do not need an unconfirmed exploit name to act on CERT-FR’s access restrictions and recovery guidance, while the investigation determines the attack’s full scope.
References
- Dominique Schelcher, Coopérative U. Statement on the overnight refrigeration cyberattack. October 12, 2026; accessed October 13, 2026.
- CERT-FR. Security incident targeting remote controllers of refrigeration installations. CERTFR-2026-ALE-012, first issued October 12; updated and accessed October 13, 2026.
- CERT-FR. Hardening recommendations for energy and water operators. CERTFR-2025-DUR-003, January 22, 2026; accessed October 13, 2026.
- AFP. “Refrigerator temperatures soar in Swedish supermarkets: chains.” The Peninsula, November 2, 2026; accessed November 2, 2026. AFP interviews with ICA and Coop.
- Louise Rasmussen, Helen Reid, Marcus Mathiesen. European supermarkets rush to patch vulnerabilities after region-wide fridge hack. Reuters / ESM Magazine, November 3, 2026; accessed November 4, 2026.
- CISA, FBI, HHS, USDA, DoT. US Government Partners Urge Hardening Industrial Refrigeration and Cold Chain Monitoring Systems. November 5, 2026; accessed November 6, 2026.
- Unit 42, Palo Alto Networks. Turning Up the Heat: Inside the Attacks on Europe’s Refrigeration System. November 6, 2026.
- ANSSI. CERT-FR / C4 technical report on the October refrigeration attack. November 9, 2026.
- National Cyber Security Centre, Ireland. New Vulnerabilities in Refrigeration Controllers. November 13, 2026; accessed November 16, 2026.